550

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Sequence
If all requirements mentioned before have been met, the brake test can be started by setting the

input BRK_bBrakeTest to TRUE.

[11-47] Sequence of the brake test

Error behaviour
If during the brake test the stop position of the motor axis has changed by more than the

permissible angle of rotation set in

C02595

, although the brake is engaged:

• The brake test is cancelled immediately and "Quick stop by trouble" is activated as error

response to avoid a further rotation/acceleration of the drive.

• The error message "Motor brake: Angular drift with closed brake too high" is entered into the

logbook.

• The status "position drift when brake is applied" is displayed for one cycle at the BRK_dnState

status output via bit 21 and the status "brake error" is displayed via bit 15.

• The BRK_bError output is set to TRUE for one task cycle.

 Normal behaviour

 Error behaviour

C02594

: Test torque

C02595

: Permissible angle of rotation

CINH = controller inhibit

• The specified test torque is created via a

ramp generator with an acceleration time

of 1 s and held max. 4 s.

• By this the motor shaft tries to rotate

while the brake is applied.

• By resetting the input BRK_bBrakeTest to

FALSE the brake test can be aborted.

t

?

0
1

M

t

j

t

t

BRK_bBrakeTest

CINH

C2605/1

C2605/2





t

BRK_bError

C2605/3