5motor interface – Lenze 9400 User Manual
Page 205
Advertising
Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06
205
5
Motor interface
5.8
Parameterisable additional functions
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8. Enter the maximum process current ("15 A") in
.
9. Switch on the correction (
= "ON").
• When the correction of the stator leakage inductance is switched on, the same current
characteristic should occur, irrespective of the current magnitude.
• Since the current controller gain is corrected actively, the step responses may differ slightly
compared to the previous measurements. In this case
and
one last time.
10. Save parameter set (
= "11: Save start parameters").
Advertising
This manual is related to the following products: