How to determine the inverter error characteristic:

1. If the controller is enabled, inhibit the controller, e. g. with the device command

C00002

= "41: Inhibit controller".

2. Execute device command

C00002

= "71: Calculate inv. error characteristic".

3. The detection of the inverter error characteristic starts with the

C00002

= "42: Enable

controller" device command (or, alternatively, with the controller enable via terminal RFR).
Notes:

• By means of controller inhibit, the started procedure can be cancelled anytime, if

required. Characteristic values that have already been determined in this case are

rejected. Details on the procedure can be seen from the "Procedure" section below.

• After successful termination, the detected characteristic is set in the controller. The

inverter error characteristic must only be detected again if the controller, motor, or

motor cable has changed e.g. due to an exchange.

The following device commands are used to terminate the successful procedure:

4. Device command

C00002

= "11: Save start parameters" for a permanent acceptance of the

characteristic.

5. Device command

C00002

= "41: Inhibit controller"

6. Device command

C00002

= "42: Enable controller"

Tip!
For controller enable all sources for controller inhibit must be reset. In

C00158

the sources

for controller inhibit are displayed in a bit-coded manner.
The status of the device command activated under

C00002

is indicated under

C00003

.