I-1003, 9"can on board" system bus – Lenze 9400 User Manual

Page 342

Advertising
background image

9

"CAN on board" system bus

9.10

Implemented CANopen objects | I-1003

342

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

I-1003

Error history
This object indicates that an error has occurred in the module and in the standard device.

Index:

I-1003

Name:

Predefined error field

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Number of errors

0

0

255 rw

U8

1 ... 10: Standard error field

-

0

4294967295 ro

U32

Subindex

Meaning

0

Number of saved error messages

1 ... 10

Display of the error list

The error messages (U32) consist of a 16-bit error code and a manufacturer-specific

information field comprising 16 bits.

Note!

The values in the "standard error field" under subindex 1 ... 10 will be deleted if the

subindex "number of recorded errors" is overwritten with the value "0".

Emergency

error code

Cause

Entry in the error

register

(

I-1001

)

0x0000

One of several errors eliminated

0xXX

Elimination of one single error

(afterwards error-free state)

0x00

0x1000

Standard device is in error status (error response "fault", "message",

"warning", "error", "quick stop by trouble", or "system error")

0x01

0x3100

Supply voltage of standard device faulty or failed

0x01

0x8100

Communication error (warning)

0x11

0x8130

Life guard error or heartbeat error

0x11

0x8150

Collision of COB-IDs: An ID parameterised for reception is also used

for transmission.

0x11

0x8210

PDO length shorter than expected

0x11

0x8220

PDO length greater than expected

0x11

0x8700

Monitoring of the sync telegram

0x11