3 process when brake is closed, 11 basic drive functions – Lenze 9400 User Manual

Page 543

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

543

11

Basic drive functions

11.12

Brake control

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11.12.5.3 Process when brake is closed

The following process occurs if the enable of the requested basic function for traversing the drive is

deactivated again:

1. The drive is brought to standstill via the basic function "

Stop

", or, where required, also via the

basic function "

Quick stop

".

2. When speed setpoint and actual speed value have fallen below the speed threshold set in

C02581

:

• The output BRK_bReleaseBrakeOut is set to FALSE for closing the brake.
• The current torque is saved, so that, if necessary, it can be used for feedforward control

during the next start.

• Monitoring of the motor brake control module is deactivated temporarily.
• Monitoring of the status input is deactivated temporarily (if switched active via

C02583

).

• The elapse of the brake application time starts.

3. After the brake closing time has elapsed and the corresponding state change of the status

signal:

• The output BRK_bBrakeReleased is reset to FALSE.
• The controller inhibit is activated.

4. After the additional waiting time set for the status monitoring in

C02591

has elapsed:

• Monitoring of the motor brake control module is active again.
• Monitoring of the status input is active again (if switched active via

C02583

).

• Standstill monitoring is activated.

Standstill monitoring

( 526)