Can module (mxi1): bus off [0x009d0000, 0x009d0000, 0x009d0001 – Lenze 9400 User Manual

Page 684: 0x00990004, 0x00990005, 13 diagnostics & fault analysis

Advertising
background image

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

684

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

DFIN (MXI1): Supply cannot be corrected anymore [0x00990004]

DFOUT (MXI1): Maximum frequency reached [0x00990005]

CAN module (MXI1): Bus off [0x009d0000]

CAN module (MXI1): Invalid node address 0 [0x009d0001]

Module ID (decimal)

Error ID (decimal)

153: Extension module - digital frequency in MXI1

4

Response (Lenze setting printed in bold)

Setting:

C13042

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Digital frequency extension module in MXI1: The

encoder voltage controlled by the digital frequency input

has reached the voltage limit.

Check encoder.

Module ID (decimal)

Error ID (decimal)

153: Extension module - digital frequency in MXI1

5

Response (Lenze setting printed in bold)

Setting:

C13080

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Digital frequency extension module in MXI1: Limit

frequency at the digital frequency output reached.

• The digital frequency has reached the limit value set

in

C013053

.

Check limit value set.

Module ID (decimal)

Error ID (decimal)

157: CAN module in MXI1: CAN dispatcher

0

Response (Lenze setting printed in bold)

Setting:

C13595

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: "Bus-off"

state

• Received too many faulty telegrams.

• Defective cable (e.g. loose contact).

• Two nodes with the same ID.

• Remove fault (e.g. EMC).

• Remove loose contact, screw down adapter.

• Assign different IDs to nodes.

Module ID (decimal)

Error ID (decimal)

157: CAN module in MXI1: CAN dispatcher

1

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: Initialisation

error

• The hardware allocation of the node address was

selected via DIP switches, and the DIP switches of the

node address are all on zero.

Note: Instead of the impermissible node address 0, node

address 1 is used.

• Set a non-zero node address by means of the DIP

switches and then switch mains.

• Activation of the software allocation of the node

number by switching over DIP switch 2, then switch

mains.