Jerk has been limited [0x00b8000e, Maximum speed exceeded [0x00b80010, Maximum acceleration exceeded [0x00b80011 – Lenze 9400 User Manual

Page 701: 0x00b8000e, 0x00b80011, 0x00b80010, 0x00b8000f, 13 diagnostics & fault analysis

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

701

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Jerk has been limited [0x00b8000e]

Position target outside the software limit positions [0x00b8000f]

Maximum speed exceeded [0x00b80010]

Maximum acceleration exceeded [0x00b80011]

Module ID (decimal)

Error ID (decimal)

184: Basic drive functions

14

Response (Lenze setting printed in bold)

Setting:

C02716/3

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The requested S-ramp time is lower than the minimum

S-ramp time set in

C02706

and has been limited to this S-

ramp time.

• Increase S-ramp time of the traversing profile of the

basic function (manual jog, homing, or positioning).

• Reduce minimum S-ramp time (

C02706

).

• Deactivate monitoring of the limit values by the basic

function "Limiter".

Module ID (decimal)

Error ID (decimal)

184: Basic drive functions

15

Response (Lenze setting printed in bold)

Setting:

C02716/2

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

It was tried to position to a target outside the software

limit positions.

• Select a target within the software limit positions.

• Increase permissible traversing range (change setting

of the software limit positions).

• Deactivate monitoring of the software limit positions

by the basic function "Limiter".

Module ID (decimal)

Error ID (decimal)

184: Basic drive functions

16

Response (Lenze setting printed in bold)

Setting:

C02716/3

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The max. speed parameterised in

C02703

or

C00011

has

been exceeded.

• Reduce speed.

• Increase maximum speed (

C02703

).

• Deactivate monitoring of the limit values by the basic

function "Limiter".

Module ID (decimal)

Error ID (decimal)

184: Basic drive functions

17

Response (Lenze setting printed in bold)

Setting:

C02716/3

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The max. acceleration parameterised in

C02705

has

been exceeded.

• Reduce acceleration.

• Increase maximum acceleration (

C02705

).

• Deactivate monitoring of the limit values by the basic

function "Limiter".