Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

139

5

Motor interface

5.3

Adjusting motor and controller to each other

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

• The motor parameters listed in the following table are excluded from the automatic

determination and must be adapted to the motor used (see motor nameplate) before the

determination.

How to determine the motor parameters:

1. If the controller is enabled, inhibit the controller, e. g. with the device command

C00002

= "41: Inhibit controller".

2. Execute device command

C00002

= "72: Determine motor parameters".

The procedure starts with controller enable, if

• no other identification is active,
• no error has occurred, and
• no test mode is activated.

If one of the above conditions is not met, the procedure is cancelled and the corresponding

device command status is indicated under

C00003

.

Note:

By means of controller inhibit, the started procedure can be cancelled anytime, if required,

without altering the codes for the motor parameters.
For detailed information about the procedure, please see the following section "Sequence".

Parameter

Info

C00081

Rated motor power

C00084

Motor stator resistance

(Default setting is used as starting value for the automatic determination.)

C00087

Rated motor speed

C00088

Rated motor current

(The current amount for the procedure is derived from this specification)

C00089

Rated motor frequency

C00090

Rated motor voltage

Note!

For devices of the types 9 + 10 (from 132 kW) the automatic determination of the motor

parameters may fail and a corresponding status display is output.
Remedy: Parameterise the motor parameters manually by means of the manufacturer's

data sheet.