5

Motor interface

5.3

Adjusting motor and controller to each other

140

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Tip!
For controller enable all sources for controller inhibit must be reset. In

C00158

the sources

for controller inhibit are displayed in a bit-coded manner.
The status of the device command activated under

C00002

is indicated under

C00003

.

Sequence
If all conditions are met, the impedance of the controlled system is determined for approx. 30

different frequencies. These values are used to determine the electrical machine parameters by

means of a mathematical procedure.

• Since the procedure starts with very low frequencies and always considers several complete

periods, the whole process takes approx. 3 minutes.

• During the procedure, the motor is energised with a current, the r.m.s. value of which

corresponds to the lower of the following two values:

After the parameters have been extracted from the impedance, they are checked for consistency

with the required rated values. If an inconsistent parameter set is detected, is this an indication of

faulty rated values on the nameplate.

After successful completion...
...controller inhibit is set automatically and the motor data determined are set in the corresponding

codes.

• For a permanent acceptance of the settings, the parameter set must be saved (

C00002

= "11:

Save start parameters").

• With the device command

C00002

= "42: Enable controller" the controller inhibit set

automatically during the procedure can be deactivated again.

or

Note!

During the procedure, the motor should not rotate.
With synchronous machines, this cannot always be ensured. Although the current flow

is produced in the torque-neutral axis, asymmetries in the machine lead to a rotation of

the rotor.

• In such a case, the measurement would be useless and would have to be repeated.
• As a remedy, we recommend to use a holding brake.

With asynchronous machines, slight rotations might possibly occur. Their influence on

the measurements is, however, not worth mentioning.

• In case of uncertainties, the measurement should be repeated several times to check

if the results for the stator resistance, the leakage inductance of the stator and the

rotor resistance differ widely. This should not be the case.

• The magnetising inductance and the cos(ϕ) values are not that important for the

diagnostics, because they are strongly non-linear.

Rated device current

1

2

---

Rated motor current