5

Motor interface

5.6

V/f control (VFCplus)

192

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Identification of the oscillation
Before the oscillation damping can be parameterised, the oscillation has to be identified. One way

is to examine the motor current while oscillation damping is switched off (

C00967

= 0 %). At steady-

state operation, a constant current flows. If the drive oscillates, these oscillations are also visible on

the motor current. It is therefore possible to determine the frequency and the amplitude of the

oscillation from the alternating component of the motor current. In the following, this alternating

component is referred to as "current oscillation".

Parameter setting

• The time constant (

C00968

) is determined from the reciprocal value of twice the frequency of

the current oscillation:

• The gain factor (

C00967

) is calculated with the following formula based on the relationship

between the amplitude of the current oscillation and the maximum device current:

• The maximum oscillation frequency (

C00969

) serves to the absolute limitation of the oscillation

frequency calculated before it is added to the field frequency. It can be derived from the

amplitude of the current oscillation, the rated motor current, and the slip frequency of the

motor connected:

From software version V5.0:

The ramp end frequency (

C00970

) defines the rotational frequency

from which the gain factor is to have reached its nominal value (

C00967

).

• The ramp end frequency refers to the rated motor frequency in percent (

C00089

).

• Below a speed of 10 rpm, the oscillation damping remains deactivated.
• For machines with a power greater than 55 kW a ramp end frequency of 20 % is

recommended.

Short overview: Parameters for oscillation damping

Parameter

Info

Lenze setting

Value Unit

C00967

VFC: Gain - oscillation damping

20 %

C00968

VFC: Time const. - oscill. damp.

5 ms

C00969

VFC: Limitation - oscillation damping

0.2 Hz

C00970

VFC: Ramp end freq. - oscillation damping

0 %

Time constant

1

2 Oscillation frequency

--------------------------------------------------------------

=

Gain

Current amplitude

2 Maximum device current (C00789)

------------------------------------------------------------------------------------------------------

100 %

=

Max. frequency

2 Amplitude of the current oscillation

Rated motor current

----------------------------------------------------------------------------------------------------

Rated slip frequency

=