Parameter setting of quick stop

[11-11] Deceleration time referred to the motor reference speed

[11-12] Deceleration time referred to the current speed

[11-13] S-shaped deceleration ramp through selection of a relative S-ramp time

Tip!
After reaching standstill, the standstill position can be maintained while a torque is

applied.

• For this purpose, select the phase controller gain in

C00254

> "0".

• With

C00254

> "0" the phase control is automatically activated after the standstill is

reached.

• The deceleration time for the quick stop

function set in

C00105

refers to a speed

variation from the motor reference speed

(

C00011

) to standstill.

n

t

C00011

C00105

TRUE

FALSE

bActivate1...3

t

• When

C00107

is set = "1", the deceleration

time refers to the current speed.

C00105

n

t

C00011

• By entering a relative S-ramp time in

C00106

, the deceleration ramp can be set

in an S-shaped manner for purposes of jerk

limitation; the total time until standstill is

then extended by the S-ramp time

set.

Setting the S-ramp time

( 382)

• Braking time at motor reference speed or

C00107

= "1":

n

t

C00011

n

t

C00011

C00107 = 0

C00107 = 1

C00105 +

C00105 C00106

×

100 %

C00105 C00105 C00106 [%]

100 %

------------------------------------------------------

+