5motor interface – Lenze 9400 User Manual

Page 179

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

179

5

Motor interface

5.5

Sensorless vector control (SLVC)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5. Evaluate the step response:

6. Change the gain Vp under

C00075

and the reset time Tn under

C00076

.

7. Repeat steps 4 ... 6 until the optimum step response of the motor current is reached.

• In the optimised state the current rise time typically is 0.5 ... 1 ms.

8. After the optimisation has been completed, deactivate the test mode again (

C00398

= "0:

Test mode deactivated").

9. Save parameter set (

C00002

= "11: Save start parameters").