Connecttable active [0x008c001a, Internal error (crc application) [0x008c001d, Parameter set faulty [0x00900000 – Lenze 9400 User Manual

Page 675: 0x008c001a, 0x008c001d, 0x00900000, 0x008c001e, 13 diagnostics & fault analysis

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

675

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

ConnectTable active [0x008c001a]

Internal error (CRC application) [0x008c001d]

Storage capacity for user parameters exceeded [0x008c001e]

Parameter set faulty [0x00900000]

Module ID (decimal)

Error ID (decimal)

140: Application project manager

26

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The application is provided with a so-called connection

table, i. e. connections can be altered "online" in the

function block editor without having to carry out a new

complete download.

- (Information only)

Module ID (decimal)

Error ID (decimal)

140: Application project manager

29

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

• The checksum of the application is faulty.

• Files required to run the application are missing.

• The supply voltage failed before the entire parameter

set could be saved.

Transmit the application to the controller again.

Module ID (decimal)

Error ID (decimal)

140: Application project manager

30

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Due to the creation of too many user parameters within

the application, the storage capacity available on the

memory module has been exceeded. User parameters

are produced directly by manual creation or indirectly by

the insertion of function blocks.

• Use an MM4xx memory module instead of the

MM3xx type (approx. twice the storage capacity).

• Remove unnecessary, manually created user

parameters from the application.

• Remove unnecessary function blocks from the

application.

• Recompile the application and download it again.

• Acknowledge the error.

Then the current utilisation of the memory can be

assessed using code

C02112

. If 100 % is displayed, this

corresponds to the maximum utilisation for an

executable application.

Module ID (decimal)

Error ID (decimal)

144: Parameter manager

0

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Parameter set is invalid.

Transfer parameter set from Engineer to the controller

and save with

C00002

="11".