Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

181

5

Motor interface

5.6

V/f control (VFCplus)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.6

V/f control (VFCplus)

This function extension is available from software version V3.0!

If this motor control mode is set in

C00006

, the output voltage of the controller follows a firmly

defined characteristic.

5.6.1

Basic settings

After the motor and controller have been optimally adjusted to each other, the "initial

commissioning steps" described in the following table are sufficient for a simple characteristic

control.

• Detailed information on the individual steps can be found in the following subchapters.

Tip!
How to optimise the control behaviour and adjust it to the concrete application is described

in the chapter "

Optimising the control mode

".

( 188)

Parameterisable additional functions are described correspondingly in the chapter

"

Parameterisable additional functions

".

( 200)

Note!

The operation of vertical drives/hoists is only supported up to 55 kW by the V/f control!

Initial commissioning steps

1.

Defining the V/f characteristic

.

( 182)

2.

Setting the voltage boost

.

( 183)

3.

Parameterising load adjustment

.

( 185)

4.

Activating voltage vector control

.

( 186)

• The Voltage Vector Control (VCC), which can be activated, serves to provide a torque at low field

frequencies. This task is executed by a current controller the output voltage of which is added to the

voltage from the characteristic.

5.

Defining the current limit (Imax controller)

.

( 187)

6. Additional "flying restart" function:

• In the Lenze setting, this parameterisable additional function is activated.

• If the flying restart function is not required, deactivate this function.

Flying restart function ( 209)

Only deactivate the flying restart if it is ensured that the drive is always at standstill in the case of controller

enable!

7. Additional "DC-injection braking" function:

• In the Lenze setting, this parameterisable additional function is deactivated.

• If DC-injection braking is required, activate this function.

DC-injection braking ( 212)