3 optimising the control mode, Optimising the control mode, The chapter – Lenze 9400 User Manual

Page 172: 5motor interface

Advertising
background image

5

Motor interface

5.5

Sensorless vector control (SLVC)

172

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.5.3

Optimising the control mode

A manual optimisation of the controller settings may be required for very dynamic applications and

in the field weakening range.

Based on the typical controller settings which are listed in the chapter "

Parameterising speed and

torque controller

" in table

[5-8]

, first the field feedforward control and the speed controller are

optimised in the base speed range. Afterwards, the torque controller is optimised in the field

weakening range.
For optimisation, a suitable speed ramp must be selected for the drive and the acceleration must be

recorded, e.g. using the

Oscilloscope

function in »Engineer«.

( 579)

Short overview: Parameters for controller settings

Note!

The processes for optimising the controller settings described in the following

subchapters can only be executed while the drive is rotating and never when being at

standstill!
For all optimisation processes the magnetisation phase has to be completed!

Parameter

Info

Lenze setting

Value Unit

C00070

Speed controller gain

0.500 Nm/rpm

C00071

Speed controller reset time

24.0 ms

C00985

SLVC: Field controller gain

0.00

C00986

SLVC: Cross current controller gain

0.00

C00987

SLVC: Torque controller gain

0.5000 Hz/A

C00988

SLVC: Torque controller reset time

10.00 ms