1 optimising the current controller, Optimising the current controller, 5motor interface – Lenze 9400 User Manual

Page 144

Advertising
background image

5

Motor interface

5.4

Servo control (SC)

144

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.4.1.1

Optimising the current controller

An optimisation of the current controller is useful, as the two controller parameters gain (

C00075

)

and reset time (

C00076

) depend on the maximum current required and the switching frequency set.

For this purpose, the controller parameters only need to be adapted once at a fixed switching

frequency.
We recommend to select a switching frequency

• as low as possible if the controller is to be operated frequently at the maximum current limit.
• of 8 kHz (up to and including model 7) or 4 kHz (from model 8 onwards) if the maximum current

limit will not be reached or will only be reached rarely.

The controller parameters are then automatically adapted to the other switching frequencies.
In a test mode you can select current setpoint step-changes and optimise the setting of both control

parameters by evaluating the step responses.

• The starting values for gain and reset time can be calculated with the following formula:

Note!

The current controller should always be optimised if a motor of a third-party

manufacturer with unknown motor data is used!

Gain

Stator leakage inductance

340 μs

-------------------------------------------------------------------

=

Reset time

Stator leakage inductance

Stator resistance

-------------------------------------------------------------------

=

Advertising
This manual is related to the following products: