3 "ls_digitalinput" system block, Ls_digitalinput" system block, 8i/o terminals – Lenze 9400 User Manual

Page 280: Control

Advertising
background image

8

I/O terminals

8.4

Digital inputs

280

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.4.3

"LS_DigitalInput" system block

The LS_DigitalInput system block displays the digital inputs and the status of the state bus in the

function block editor.

Output

DIS code | data type

Value/meaning

DIGIN_bCInh

C00443/9

| BOOL

Status signal "Controller inhibit"

• The control input RFR (X5/pin 9) for setting/deactivating controller inhibit is

fixedly connected to the device control (DCTRL) via an inverter.

TRUE Controller inhibit active

DIGIN_bIn1

C00443/1

| BOOL

...

DIGIN_bIn8

C00443/8

| BOOL

Digital input 1 ... 8

DIGIN_bStateBusIn

C00443/12

| BOOL

State bus status

"State bus" monitoring function ( 283)

TRUE A node connected to the state bus has set the state bus to LOW level

and the "Error" state has been set.

• The "Error" state is also set if a node connected to the state bus is

not supplied with voltage.

LS_DigitalInput

DIGIN_bIn1

DIGIN_bIn2

DIGIN_bIn5

DIGIN_bIn4

DIGIN_bIn3

X5

DIGIN_bIn6

DIGIN_bIn7

DIGIN_bIn8

DIGIN_bCInh

DIGIN_bStateBusIn

1

0

1

C00114/1...8

C00443/1...8

CONTROL

GI

RFR

DI1

DI2

DI3

DI4

DI5

DI6

DI7

DI8

GE

24E

SB

X2

DriveInterface

1

Advertising