3 led status displays for the system bus, Led status displays for the system bus, 9"can on board" system bus – Lenze 9400 User Manual

Page 298

Advertising
background image

9

"CAN on board" system bus

9.3

LED status displays for the system bus

298

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.3

LED status displays for the system bus

Both upper LEDs LEDs "CAN-RUN" and "CAN-ERR" on the front of the controller inform about the

CANopen state and report CANopen errors.

[9-2]

LED status displays CAN-RUN and CAN-ERR

The meaning can be seen from the table below:

CAN-RUN

CAN-ERR

LED status display

Meaning

CAN-RUN

CAN-ERR

CANopen state

CANopen error

Only CAN-ERR is on

-

Bus off

CAN-RUN and CAN-ERR jitter

Automatic detection of the baud rate is active.

CAN-RUN is blinking every 0.2 seconds | CAN-ERR is off

Pre-operational

-

CAN-RUN is blinking every 0.2 seconds | CAN-ERR 1 x blinking, 1

s off

Warning limit reached

CAN-RUN is blinking every 0.2 seconds | CAN-ERR 2 x blinking, 1

s off

Node guard event

Only CAN-RUN is on

Operational

-

CAN-RUN on | CAN-ERR 1 x blinking, 1 s off

Warning limit reached

CAN-RUN on | CAN-ERR 2 x blinking, 1 s off

Node guard event

CAN-RUN on | CAN-ERR 3 x blinking, 1 s off

Sync message error

CAN-RUN is blinking every 1 second | CAN-ERR is off

Stopped

-

CAN-RUN is blinking every 1 second | CAN-ERR 1 x blinking, 1 s off

Warning limit reached

CAN-RUN is blinking every 1 second | CAN-ERR 2 x blinking, 1 s off

Node guard event