The LS_Stop system block provides the internal interfaces for the basic function "Stop" in the

function block editor.

Outputs

Note!

Ensure that the system block is called in a cyclic application task.
Basically, projects which only contain an unsolicited task and no cyclic task are not

permissible!

Identifier

DIS code | data type

Value/meaning

STP_dnState

C02616

| DINT

Status (bit coded)

• When the basic function is not active, all bits are set to "0".

• Bits which are not listed are not assigned with a status (always "0").

Bit 1 Drive is braked to standstill.

• The internal state machine is in the "Drive is stopped" function

state.

Bit 2 Drive is at standstill.

• The internal state machine is in the "Drive at standstill" function

state.

Bit 3 Deceleration phase is active.
Bit 5 CCW rotation is active.

STP_bStopActive

C02617

| BOOL

Status signal "Stop is active"

TRUE The drive is braked to standstill or is at standstill.

• The internal state machine is in the "Drive is stopped" or "Drive at

standstill" function state.

STP_dnState

STP_bStopActive

n

t

LS_Stop

Activate stopping

(internal status machine)