3 deactivation, Deactivation, 11 basic drive functions – Lenze 9400 User Manual

Page 411

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

411

11

Basic drive functions

11.5

Manual job, encoderless

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11.5.2.3

Deactivation

The basic function is deactivated by

• setting the input "MOL_bEnable" to FALSE or
• removing the checkmark (if there is one) in the »Engineer« dialog box entitled Manual control

(parameter set 1).

[11-21] Deactivation of the basic function "Manual jog, encoderless"

Stop!

Before the basic function is deactivated, the controller inhibit must be set. Otherwise,

unsteady drive behaviour can occur when a changeover is made from the basic function

"Manual jog, encoderless" to the basic function "Stop".