Safety module has been removed [0x00680007, Control card is defect [0x00680008, Power section is defect [0x00680009 – Lenze 9400 User Manual

Page 626: Mxi1: module is defect or missing [0x0068000a, Mxi2: module is defect or missing [0x0068000b, 0x00680008, 0x0068000a, 0x0068000b, 0x00680009, 0x00680007

Advertising
background image

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

626

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Safety module has been removed [0x00680007]

Control card is defect [0x00680008]

Power section is defect [0x00680009]

MXI1: Module is defect or missing [0x0068000a]

MXI2: Module is defect or missing [0x0068000b]

Module ID (decimal)

Error ID (decimal)

104: Module identification

7

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

You have tried to remove or change the safety module

during operation.

Switch off the controller, plug in safety module and

switch on the controller again.

• If the error occurs again, the safety module is

defective and must be replaced.

Module ID (decimal)

Error ID (decimal)

104: Module identification

8

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Operating system could not identify the control card.

Consultation with Lenze required.

Module ID (decimal)

Error ID (decimal)

104: Module identification

9

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Operating system could not identify the power section. Consultation with Lenze required.

Module ID (decimal)

Error ID (decimal)

104: Module identification

10

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Operating system could not identify the extension

module in module slot MXI1.

• Use a different extension module.

• Please contact Lenze.

Module ID (decimal)

Error ID (decimal)

104: Module identification

11

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Operating system could not identify the extension

module in module slot MXI2.

• Use a different extension module.

• Please contact Lenze.

Advertising