Pointer access in impermissible memory area [0x006a0012]

Application has started [0x006a0013]

Application has stopped [0x006a0014]

PDO mapping (MXI1): Faulty configuration [0x006a0015]

Module ID (decimal)

Error ID (decimal)

106: Runtime environment for IEC 61131-3 programs

18

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

An invalid pointer access to a protected area occurred in

the application.

Replace application.

Module ID (decimal)

Error ID (decimal)

106: Runtime environment for IEC 61131-3 programs

19

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The application in the controller has been started.

- (Information only)

Module ID (decimal)

Error ID (decimal)

106: Runtime environment for IEC 61131-3 programs

20

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The application in the controller has been stopped.

- (Information only)

Module ID (decimal)

Error ID (decimal)

106: Runtime environment for IEC 61131-3 programs

21

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: Incorrectly

configured process data mapping.

• The corresponding PDO channel is not installed, e. g.

because no communication module was selected for

module slot MXI1 in the Engineer project.

• The communication module selected for module slot

MXI1 in the Engineer project does not support PDO

mapping.

• The mapping information downloaded to the

controller is faulty.

• Integrate suitable communication module for

module slot MXI1 in the Engineer project.

• Check the configuration of the network. Then

recompile the project and transmit it to the controller.