Diagnostics & fault analysis

13.7

Error messages of the operating system

640

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Watchdog cycle is greater than task cycle [0x006a001b]

Control card: Supply voltage (24 V DC) too low [0x006f0000]

Read error service register [0x00720000]

External error [0x00750000]

Module ID (decimal)

Error ID (decimal)

106: Runtime environment for IEC 61131-3 programs

27

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

An application has been downloaded

• with the highest priority task having a smaller cycle

than the parameterised watchdog cycle

or

• with the watchdog of the highest priority task being

deactivated.

You can acknowledge the error if you follow the below

procedure:

1. Activate watchdog

2. Set a watchdog cycle that is smaller than or equal to

the task cycle

3. Recreate the application and download it again

From software version V11.0:

If the device boots with

an application without an activated watchdog or with

a watchdog set incorrectly, only an information is

entered in the logbook.

Module ID (decimal)

Error ID (decimal)

111: Monitoring of the 24V supply voltage

0

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

External 24 V supply voltage of the control card is lower

than 18 V.

Check external supply voltage.

• If the external supply voltage is available and the

error message does not disappear, please contact

Lenze.

Module ID (decimal)

Error ID (decimal)

114: Service register

0

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

During reading or writing the service register a fault has

occurred.

Mains switching

• Please contact Lenze if the problem occurs again.

Module ID (decimal)

Error ID (decimal)

117: Device control

0

Response (Lenze setting printed in bold)

Setting:

C00581

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The drive interface has activated the error message

"External error".

• The input DI_bSetExternError of the system block

LS_DriveInterface has been set to TRUE.

• Check external device to be monitored.

• Check assignment of the input DI_bSetExternError in

the application.