Diagnostics & fault analysis

13.7

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

System task 3: Task overflow [0x0091000c]

System task: Task overflow [0x0091000d]

Communication task: Standstill > 3 s [0x0091000e]

Cyclic task: Standstill > 60 s [0x0091000f]

Module ID (decimal)

Error ID (decimal)

145: Lenze runtime system

12

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

System overload.

Consultation with Lenze required.

Module ID (decimal)

Error ID (decimal)

145: Lenze runtime system

13

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

System overload.

Consultation with Lenze required.

Module ID (decimal)

Error ID (decimal)

145: Lenze runtime system

14

Response (Lenze setting printed in bold)

Setting:

C01230

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Service data communication within the system (SDO

communication of all bus systems connected) has

caused an overload of service data processing. Due to

this, the monitoring interval of the processing task has

been violated. PDO communication is not affected by

this overload.

Reduce system load.

• Reduce the data and communication volume on the

buses. Processing will restart automatically when the

overload has been eliminated.

For systems frequently affected by this type of overload,

the error response can be changed to warning via code

C01230

in order to increase the drive availability.

Module ID (decimal)

Error ID (decimal)

145: Lenze runtime system

15

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

System overload or CRC check task crash.

Reduce system load.

• This is possible in the application or data transfer of

the communication interfaces.