Position value faulty [0x00910010]

Error during initialisation [0x00910011]

Block function in wrong MEC task [0x00910012]

Safety module: Incompatible with setting in C00214 [0x00920000]

Communication with safety module interrupted [0x00920001]

Module ID (decimal)

Error ID (decimal)

145: Lenze runtime system

16

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Internal error

If the error occurs frequently, please contact Lenze.

Module ID (decimal)

Error ID (decimal)

145: Lenze runtime system

17

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Internal error

If the error occurs frequently, please contact Lenze.

Module ID (decimal)

Error ID (decimal)

145: Lenze runtime system

18

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Internal error

If the error occurs frequently, please contact Lenze.

Module ID (decimal)

Error ID (decimal)

146: Interface to the safety module

0

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The controller has detected a safety module which does

not match the setting under

C00214

.

Change setting under

C00214

or use a suitable safety

module.

• Afterwards mains switching is required.

Module ID (decimal)

Error ID (decimal)

146: Interface to the safety module

1

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

It is not possible to establish communication between

the controller and safety module.

• Switch off the controller, plug in safety module

correctly and switch on the controller again.

• If the problem occurs again, replace the safety

module.