0x00a10002, 0x00a10003, 0x00a10004 – Lenze 9400 User Manual

Page 688: 0x00a10005, 13 diagnostics & fault analysis

Advertising
background image

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

688

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CAN module (MXI1) RPDO3: Telegram not received or faulty [0x00a10002]

CAN module (MXI1) RPDO4: Telegram not received or faulty [0x00a10003]

CAN module (MXI1) RPDO5: Telegram not received or faulty [0x00a10004]

CAN module (MXI1) RPDO6: Telegram not received or faulty [0x00a10005]

Module ID (decimal)

Error ID (decimal)

161: CAN module in MXI1: CAN-PDO handler

2

Response (Lenze setting printed in bold)

Setting:

C13591/3

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: CAN-IN 3

error

• Incorrect PDO telegram length.

• Transmission error.

• Time monitoring of the PDOs has tripped.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate trouble in the environment (e. g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Module ID (decimal)

Error ID (decimal)

161: CAN module in MXI1: CAN-PDO handler

3

Response (Lenze setting printed in bold)

Setting:

C13591/4

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: CAN-IN 4

error

• Incorrect PDO telegram length.

• Transmission error.

• Time monitoring of the PDOs has tripped.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate trouble in the environment (e. g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Module ID (decimal)

Error ID (decimal)

161: CAN module in MXI1: CAN-PDO handler

4

Response (Lenze setting printed in bold)

Setting:

C13591/5

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: CAN-IN 5

error

• Incorrect PDO telegram length.

• Transmission error.

• Time monitoring of the PDOs has tripped.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate trouble in the environment (e. g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Module ID (decimal)

Error ID (decimal)

161: CAN module in MXI1: CAN-PDO handler

5

Response (Lenze setting printed in bold)

Setting:

C13591/6

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: CAN-IN 6

error

• Incorrect PDO telegram length.

• Transmission error.

• Time monitoring of the PDOs has tripped.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate trouble in the environment (e. g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Advertising
This manual is related to the following products: