Can module (mxi2): lifeguarding error [0x00ad0020, 0x00ae0000, 0x00ad0021 – Lenze 9400 User Manual

Page 693: 0x00ad0020, 13 diagnostics & fault analysis

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

693

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CAN module (MXI2): Lifeguarding error [0x00ad0020]

CAN module (MXI2): Faulty NMT slave configuration [0x00ad0021]

CAN module (MXI2): Faulty emergency configuration [0x00ae0000]

Module ID (decimal)

Error ID (decimal)

173: CAN module in MXI2: CAN-NMT handler

32

Response (Lenze setting printed in bold)

Setting:

C14614

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: Cyclic node

monitoring

• Slave response: Maximum time between two node

guarding telegrams (remote transmission request

telegram) from the master has been exceeded.

Select a different Lifeguarding monitoring time or switch

off monitoring.

Module ID (decimal)

Error ID (decimal)

173: CAN module in MXI2: CAN-NMT handler

33

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: A

configuration error has occurred in the network

management of the CAN slave.

• Faulty download of an Engineer or PLC Designer

project

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Incorrect parameterisation of node guarding or

heartbeat.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Module ID (decimal)

Error ID (decimal)

174: CAN module in MXI2: CAN emergency handler

0

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: CAN

emergency configuration is faulty.

• Faulty download of an Engineer or PLC Designer

project

• Invalid CAN emergency settings according to

DS301V402 in the Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.