0x00b00008, 0x00b00005, 0x00b00006 – Lenze 9400 User Manual

Page 696: 0x00b00007, 13 diagnostics & fault analysis

Advertising
background image

13

Diagnostics & fault analysis

13.7

Error messages of the operating system

696

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CAN module (MXI2) RPDO6: Telegram not received or faulty [0x00b00005]

CAN module (MXI2) RPDO7: Telegram not received or faulty [0x00b00006]

CAN module (MXI2) RPDO8: Telegram not received or faulty [0x00b00007]

CAN module (MXI2) PDO manager: Faulty configuration [0x00b00008]

Module ID (decimal)

Error ID (decimal)

176: CAN module in MXI2: CAN-PDO handler

5

Response (Lenze setting printed in bold)

Setting:

C14591/6

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: CAN-IN 6

error

• Incorrect PDO telegram length.

• Transmission error.

• Time monitoring of the PDOs has tripped.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate trouble in the environment (e. g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Module ID (decimal)

Error ID (decimal)

176: CAN module in MXI2: CAN-PDO handler

6

Response (Lenze setting printed in bold)

Setting:

C14591/7

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: CAN-IN 7

error

• Incorrect PDO telegram length.

• Transmission error.

• Time monitoring of the PDOs has tripped.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate trouble in the environment (e. g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Module ID (decimal)

Error ID (decimal)

176: CAN module in MXI2: CAN-PDO handler

7

Response (Lenze setting printed in bold)

Setting:

C14591/8

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: CAN-IN 8

error

• Incorrect PDO telegram length.

• Transmission error.

• Time monitoring of the PDOs has tripped.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate trouble in the environment (e. g. EMC).

• Select a different time monitoring or switch off time

monitoring.

Module ID (decimal)

Error ID (decimal)

176: CAN module in MXI2: CAN-PDO handler

8

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: CAN-PDO

configuration error

• Faulty project download.

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Mapping variables have incorrect CANopen indices

according to DS405.

• Repeat download.

• Correct CAN settings in the project and regenerate

project.