C00367 | can sync rx identifier, C00368 | can sync tx identifier, C00369 | can sync transmission cycle time – Lenze 9400 User Manual

Page 775: C00367, C00368, C00369/1, C00367 c00368, C00369, 14 parameter reference

Advertising
background image

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

775

14

Parameter reference

14.2

Parameter list | C00367

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00367

C00368

C00369

Parameter | Name:

C00367 | CAN SYNC Rx identifier

Data type: UNSIGNED_32

Index: 24208

d

= 5E90

h

Identifier by means of which the sync slave is to receive sync telegrams.

• Mapping of the CANopen object

I-1005

(see DS301 V4.02).

"CAN on board" system bus: sync telegram

Setting range

(min. value | unit | max. value)

Lenze setting

0

2047 128

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00368 | CAN SYNC Tx identifier

Data type: UNSIGNED_32

Index: 24207

d

= 5E8F

h

Identifier by means of which the sync master is to transmit sync telegrams.

• Mapping of the CANopen object

I-1005

(see DS301 V4.02).

"CAN on board" system bus: sync telegram

Setting range

(min. value | unit | max. value)

Lenze setting

0

2047 128

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00369 | CAN sync transmission cycle time

Data type: UNSIGNED_16

Index: 24206

d

= 5E8E

h

Cycle during which the sync master is to transmit sync telegrams.

• If "0 ms" is set (Lenze setting), no sync telegrams are generated.

• Mapping of the CANopen object

I-1006

(see DS301 V4.02).

"CAN on board" system bus: sync telegram

Setting range

(min. value | unit | max. value)

0

ms

65535

Subcodes

Lenze setting

Info

C00369/1

0 ms

Transmission cycle time for CAN on board

C00369/2

0 ms

Transmission cycle time for CAN module in MXI1/MXI2

C00369/3

0 ms

- (no meaning)

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1