Parameter reference

14.2

Parameter list | C00958

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00958

C00959

C00960

C00961

C00962

Parameter | Name:

C00958 | VFC: VVC gain

Data type: UNSIGNED_32

Index: 23617

d

= 5C41

h

From software version V3.0

V/f control

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

V/A

750.00 0.00 V/A

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 100

Parameter | Name:

C00959 | VFC: VVC reset time

Data type: UNSIGNED_32

Index: 23616

d

= 5C40

h

From software version V3.0

V/f control

Setting range

(min. value | unit | max. value)

Lenze setting

0.01

ms

2000.00 2000.00 ms

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 100

Parameter | Name:

C00960 | VFC: V/f voltage boost

Data type: INTEGER_32

Index: 23615

d

= 5C3F

h

From software version V3.0

V/f control

Setting range

(min. value | unit | max. value)

Lenze setting

0

V

1000 0 V

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00961 | VFC: Load - cw/ccw-operation

Data type: UNSIGNED_32

Index: 23614

d

= 5C3E

h

From software version V3.0

V/f control

Selection list

(Lenze setting printed in bold)

0 CW: mot. / CCW: mot.
1 CW: mot. / CCW: regen.
2 CW: regen. / CCW: mot.

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C00962 | VFC: Load adjustment

Data type: UNSIGNED_32

Index: 23613

d

= 5C3D

h

From software version V3.0

V/f control

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

200.00 20.00 %

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 100