C01120 | sync source, C01121 | sync cycle time, C01121 – Lenze 9400 User Manual

Page 832: C01120, Ed in, Time, Lected in, 14 parameter reference

Advertising
background image

14

Parameter reference

14.2

Parameter list | C01120

832

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C01120

C01121

Parameter | Name:

C01120 | Sync source

Data type: UNSIGNED_8

Index: 23455

d

= 5B9F

h

Selection of the source for the synchronisation signals.

• The drive can only be synchronised by one source.

Note:

Set the selection "2: CAN module" for the communication module CANopen (E94AYCCA).

"CAN on board" system bus: sync telegram

Selection list

(Lenze setting printed in bold)

0 Off
1 CAN on-board
2 CAN module
4 Module in MXI1
5 Module in MXI2
6 Digital input 1
7 Digital input 2
8 Digital input 3
9 Digital input 4

10 Digital input 5
11 Digital input 6
12 Digital input 7
13 Digital input 8

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C01121 | Sync cycle time

Data type: UNSIGNED_32

Index: 23454

d

= 5B9E

h

Time interval at which the phase control loop (PLL) in the controller expects the synchronisation signals.

• The time interval set must correspond to the cycle of the synchronisation source.

Note: For synchronisation via the system bus (CANopen), only integer multiples of 1000 μs should be set.

Example: For the system bus, the interval between two synchronisation signals is set to 2 ms. If the system bus is to

be used as the synchronisation source, a synchronisation cycle of 2000 μs must be set in C01121.

"CAN on board" system bus: sync telegram

Setting range

(min. value | unit | max. value)

Lenze setting

250

μs

20000 1000 μs

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1