C02830 | digital inputs: delay time, C02830, 14 parameter reference – Lenze 9400 User Manual

Page 900

Advertising
background image

14

Parameter reference

14.2

Parameter list | C02830

900

Lenze · Servo-Inverter 9400 HighLine · Reference manual · DMS 10.0 EN · 11/2013 · TD05/06

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C02830

C02850

C02851

C02852

Parameter | Name:

C02830 | Digital inputs: Delay time

Data type: UNSIGNED_8

Index: 21745

d

= 54F1

h

Input filter for digital inputs

• Can be used to filter out "spikes" at the digital inputs, if necessary.

• Each digital input is assigned to a subcode.

• Since the filter is a "counting" filter, the indicated times are only approximate values.

Selection list

(Lenze setting printed in bold)

Info

0 2 μs

Filter time

1 4 μs
2 8 μs
3 16 μs
4 32 μs
5 64 μs
6 128 μs
7 256 μs
8 512 μs
9 1024 μs

10 2048 μs
11 4096 μs
12 8192 μs
13 16384 μs
14 32768 μs

Subcodes

Lenze setting

Info

C02830/1

0: 2 μs

Setting for digital input 1 ... 8

C02830/...
C02830/8

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 1

Parameter | Name:

C02850 | Service code

Data type: UNSIGNED_32

Index: 21725

d

= 54DD

h

This code is for device-internal use only and must not be written to by the user!

Parameter | Name:

C02851 | Service code

Data type: UNSIGNED_32

Index: 21724

d

= 54DC

h

This code is for device-internal use only and must not be written to by the user!

Parameter | Name:

C02852 | Service code

Data type: UNSIGNED_16

Index: 21723

d

= 54DB

h

This code is for device-internal use only and must not be written to by the user!

Advertising
This manual is related to the following products: