Power Connections

7-5

Motor Overload Protection

The drive utilizes solid state motor overload protection which
operates:

within 8 minutes at 200% overload

within 20 seconds at 600% overload

Table 7.2:

Motor Power Contact and Wire Sizing Recommendations

Motor

Motor Power Mating

Maximum

Contact Size

Minimum

Recommended 90°C

Power Wire

a

mm

2

AWG

2

mm

2

AWG

2

H-2005

1.5

16

1.5

16

H-3007

1.5

16

1.5

16

H-3016

1.5

16

1.5

16

H-4030, F-4030

4.0

12

1.5

16

H-4050, F-4050

4.0

12

2.5

14

H-4075, F-4075

4.0

12

2.5

14

H-6100, F-6100

10.0

8

4.0

12

H-6200, F-6200

10.0

8

10.0

8

H-6300, F-6300

10.0

8

10.0

8

H-8350

25.0

4

16.0

6

H-8500

25.0

4

16.0

6

N-Series

1.5

16

1.5

16

Y-Series

1.5

16

1.5

16

a. Recommendations are based on motor ratings only. If the drive in the system cannot deliver rated

power to the motor, then smaller wire sizes may be required for connection to the drive.