Auxiliary power, Auxiliary power terminals, Auxiliary power sizing requirements – Rockwell Automation 1398-DDM-xxx USE MNL/ULTRA 200 DIG.SERVO.DR User Manual

Page 120: E 7-10, Ge 7-10

Advertising
background image

Publication 1398-5.0 – October 1998

7-10

Power Connections

The inputs to the main (logic and motor supply) and the auxiliary
(logic supply only) power sources are separated. This permits the
logic power to operate independently of the motor. This dual power
sourcing is useful for troubleshooting and diagnostics.

Auxiliary Power

Auxiliary AC (Terminals 10 and 11) supplies power to the logic/
control circuits and fault logic. The main and auxiliary power must be
connected in phase.

AUX power is supplied to a switching power supply. This input
accepts Voltages from 100 to 240 VAC rms single phase with an input
frequency 47-63 Hz.

The auxiliary (logic supply only) and the main (logic and motor
supply) power sources are separated. This permits the logic power to
operate independently of the motor. This dual power sourcing is
useful for troubleshooting and diagnostics.

Table 7.6:

Auxiliary Power Terminals

Signal

Description

Terminal

1398-DDM-010,

1398-DDM-010X

1398-DDM-020,

1398-DDM-020X

1398-DDM-030,

1398-DDM-030X

1398-DDM-075,

1398-DDM-075X

1398-DDM-150,

1398-DDM-150X

L1 AUX

Auxiliary 100/240 Volts AC Line 1 input

TB1-10

TB1-11

L2 AUX IN

Auxiliary 100/240 Volts AC Line 2 input (or neu-
tral)

TB1-11

TB1-12

NOTE: Torque all terminal connections to 1.25 Nm (11.0 lb-in).

Table 7.7:

Auxiliary Power Sizing Requirements

Voltage

Input

(Volts AC)

Current

Requirements

Input

1

(Amps AC)

Inrush

(Amps peak)

Wire

mm

2

(AWG)

Transformer

2

(VA)

100

1.0

47

1.5 (16)

250

240

0.5

95

1.5 (16)

250

1. Dual element, time delay (slow acting) fuses are required to accommodate inrush
current at the auxiliary terminals during power-up. Local regulations must be
observed when selecting fuses.

2. The ULTRA 200 Series drives do

not require an isolation transformer. The recom-

mended transformer sizes are the minimum that is adequate for most servo applica-
tions. Larger transformers provide an additional safety factor. The additional safety
factor may occur in applications that require minimum bus voltage sag when the
motor must accelerate to high speed in minimum time or in applications with high con-
tinuous power requirements.

Advertising