Publication 1398-5.0 – October 1998

Application and Configuration Examples

8-21

5. Close the toggle switch between J1-26 and J1-20 to enable the

drive.

6. Choose

S

tart

from the Tuning window. The drive powers the

motor shaft for a short period and then motion will cease. Then
ULTRA Master displays the calculated gains and disables the
drive.

7. Choose

N

ormal Drive Operation

from the Tuning window.

8. Open the switch between J1-26 and J1-20 to disable the drive.

9. Choose

C

lose

to exit the Tuning window.

10. Close any open windows or dialog boxes.

Operation

The drive is now configured as a Position Follower (Step/Direction).

The servo parameters have been setup with the unloaded motor.

The motor position is controlled by the step/direction inputs.

The firmware saves the parameters in EEPROM memory. Thus the
drive can be power cycled and, after power-up, will use the
parameters selected in the steps above.

When motion is required:

1. Close the switch between J1-26 and J1-20 to enable the drive.

2. Close the toggle switch between J1-26 and J1-32 to enable fol-

lowing.

!

Intro

ATTENTION: Rotating motor shafts can cause extensive
damage and injury. Motors must be properly guarded dur-
ing testing and installation.