Testing digital inputs, Testing analog outputs – Rockwell Automation 1398-DDM-xxx USE MNL/ULTRA 200 DIG.SERVO.DR User Manual

Page 202

Advertising
background image

Publication 1398-5.0 – October 1998

11-14

Maintenance and Troubleshooting

Testing Digital Inputs

This test verifies the functionality of the selectable inputs.

Test equipment requirements are:

A PC running ULTRA Master

A jumper wire.

It assumes there are no error codes displayed, and the 24V power
supply is connected correctly.

1. Enable the drive by closing the switch connecting J1-26 and J1-

20.

2. Choose the I/O Display command icon from the Drive Window.

A. Connect J1-20 to J1-26. The Enable indicator activates.

B. Connect J1-21 to J1- 26. The Reset Faults indicator activates.

C. Connect J1-31 to J1-26. The Input 1 indicator activates.

D. Connect J1-32 to J1-26. The Input 2 indicator activates.

E. Connect J1-33 to J1-26. The Input 3 indicator activates.

F. Connect J1-33 to J1-26. The Input 4 indicator activates.

3. Choose

Close

to exit the I/O Display window.

If you determine that a digital input is defective, return the unit for
repair.

Testing Analog Outputs

The following tests verify the functionality of the analog outputs.

Test equipment requirements are:

A PC running ULTRA Master

A voltmeter.

Testing Analog Output 1

1. Disable the drive, by opening the connections between the

ENABLE input and the + 24 VDC.

2. Disconnect the connections to J1-30.

3. From the Output Diagnostics window select

Analog Output 1

.

4. Enter 1000 in the D/A level box.

5. Connect a DC voltmeter across analog test points A1 and COM.

The meter should read approximately 1 Vdc.