Publication 1398-5.0 – October 1998

Application and Configuration Examples

8-3

Configuration

Carefully check all connections before entering these parameters.

1. Switch the AC Power to ON and verify:

• green DC BUS LED is ON

• display shows an operational status: A, F or P (Analog, Fol-

lower or Preset mode of operation). Refer to “Operating Mes-
sages” on page 10-1 f
or an explanation of the display codes.

2. Start ULTRA Master on the PC.

3. Choose

Cancel

from the Drive Select dialog box.

4. Select

P

C Set Up

from the Communications menu in

ULTRA Master to display the personal computer’s communica-
tion settings.

5. Verify the communications port settings of the PC match those of

the drive.

• If the settings are correct, select

OK

in the Port – Settings dia-

log box.

• If the settings are different, correct the Port – Settings to allow

communications with the drive.

Factory default communications Port – Settings for the drive
are:

– Baud Rate:

9600

– Data Bits:

8

– Parity:

None

– Stop Bits:

1

– Serial Port:

COM1

Refer to the section “RS-232 Communication Test” on page 11-11
for troubleshooting instructions.

6. Select

R

ead Drive Parameters

from the Communications menu.

7. Verify the Drive Name and Address are correct for the drive that

is being addressed.

8. Choose

OK

to load the drive parameters.

Note: A motor must be selected for the parameters to load.