Publication 1398-5.0 – October 1998

Application and Configuration Examples

8-5

5. Close the toggle switch between J1-26 and J1-20 to enable the

drive.

6. Choose S

tart

from the Tuning window. The drive powers the

motor shaft for a short period and then motion will cease. Then
ULTRA Master displays the calculated gains and disables the
drive.

7. Open the switch between J1-26 and J1-20 to disable the drive.

8. Choose N

ormal Drive Operation

from the Tuning window.

9. Choose

Close

to exit the Tuning windows.

10. Close any open windows or dialogs.

Operation

The drive is now configured as an Analog Controller in either the
velocity or torque mode.

The current loop is compensated properly for the selected motor.

The servo parameters have been setup with an unloaded motor.

The motor speed or current is commanded through the analog
input.

The firmware saves the parameters in EEPROM memory. Thus the
drive can be power cycled and, after power-up, will use the
parameters selected in the steps above.

When motion is required:

1. Close the switch between J1-26 and J1-20 to enable the drive.

!

Intro

ATTENTION: Rotating motor shafts can cause extensive
damage and injury. Motors must be properly guarded dur-
ing testing and installation.