Specifications

G-5

Power

Table G.1:

ULTRA 200 Series Power Ratings

1398-DDM-

010,

1398-DDM-

010X

1398-DDM-

020,

1398-DDM-

020X

1398-DDM-

030,

1398-DDM-

030X

1398-DDM-

075,

1398-DDM-

075X

1398-DDM-

150,

1398-DDM-

150X

Auxiliary AC Input

Voltage

(rms Volts nominal)

Frequency

(Hz)

Current

(A

rms

@ 100 V

rms

)

(A

rms

@ 240 V

rms

)

100 to 240

47 - 63

1.0
0.5

100 to 240

47 - 63

1.0
0.5

100 to 240

47 - 63

1.0
0.5

100 to 240

47 - 63

1.0
0.5

100 to 240

47 - 63

1.0
0.5

Main AC Input

Voltage

(rms Volts nominal)

Frequency

(Hz)

Current

(rms Amps)

100 to 240,
1

47 - 63

10

100 to 240,
1

47 - 63

19

100 to 240,
1

47 - 63

28

100 to 240,
1

or 3

47 - 63

30

100 to 240,
3

47 - 63

46

Bus Voltage

(Volts

DC)

141-339 141-339 141-339 141-339 141-339

Peak Output Current

(Amps )

10

20

30

50, 1

75, 3

150

Continuous Output
Current

(Amps )

5

10

15

15, 1

35, 3

65

Peak Shunt Power
(built in resistor)

(kWatts)

4.5 4.5 4.5 10.0

18.0

Continuous Shunt Power
(built in resistor)

(Watts)

50 50 50 50 180

Peak Shunt Power
(external resistor)

(kWatts)

6.0 6.0 6.0 10.0

19.0

Continuous Shunt Power
(external resistor)

(kWatts)

2.4 2.4 2.4 4.0 8.0

Bus Capacitance Energy
Absorption
(from 325-420 Vdc Bus)

a

(Joules)

41 69 97 152

266

Advertising