Publication 1398-5.0 – October 1998

Maintenance and Troubleshooting

11-7

+5V Fuse Blown

02

F2 Blown

The fuse on the encoder
power output for the +5 VDC
power supply has tripped.

Check/replace fuse F2 if
necessary.

Check for shorts on Encoder
output signals or +5V output.

Check that J4 pin 9 or J5 pin
9 is not connected to an
external circuit.

Encoder Fuse Blown

03

F3 blown

Check for shorts on motor
Encoder signals and cable
wiring.

Check/replace fuse F3 if
necessary.

Bad encoder

Replace encoder and or
motor.

Motor Overtemperature

04

Motor TS+ (J2-19) and TS-
(J2-20) pins open

Verify TS+ (J2-19) and TS-
(J2-20) connections for con-
tinuity.

Motor thermostat trips due
to:
High motor ambient temper-
ature, and/or
Excessive RMS torque

Lower ambient tempera-
ture. Operate within (not
above) the continuous
torque rating for the ambi-
ent temperature (40°C maxi-
mum).

IPM Fault

05

Motor cables shorted

Verify continuity of motor
power cable and connector.

Motor winding shorted inter-
nally

Check for short on motor’s
R,S,T and Gnd windings.

Drive temperature too high

Check for clogged or defec-
tive fan.

Ensure cooling is not
restricted by insufficient
space around the unit.

Operation above continu-
ous power rating

Verify ambient temperature
is not too high
(above 60° C).

Operate within the continu-
ous power rating.

Output short circuit or over-
current

Drive has a bad IPM,
replace drive.

Channel IM line

06

Bad connections

Verify continuity of the
encoder cable.

Verify continuity of the IM+
and IM- wiring signals.

Bad Encoder

Replace the motor or the
encoder.

Table 11.1:

Troubleshooting Guide

(continued)

Problem or Symptom

Error Code

Possible Cause(s)

Action/Solution