Publication 1398-5.0 – October 1998

8-28

Application and Configuration Examples

Hardware Setup

Make the connections described below and shown in the Figure 8.7.
The appendix “Options and Accessories” on page A-1 lists the
interconnect cables available from the factory.

1. Connect an RS-232 cable between the serial port on the PC and

the J4 connector on the ULTRA 200 Series. A simple 3 wire cable
is depicted in the figure below.

2. Connect a Motor/Feedback cable from the motor to the J2 connec-

tor on the ULTRA 200 Series.

3. Connect a Power cable from the motor to TB1 (terminals R, S, T

and

) on the drive.

4. Connect a jumper wire with a toggle switch between the follow-

ing pins:

• J1-20 (ENABLE) and J1-26 (I/O PWR)

• J1-32 (INPUT1) and J1-26 (I/O PWR)

• J1-21 (FAULT RESET) and J1-26 (I/O PWR).

These connections provide manual control for enabling or disabling
the drive and resetting faults. The figure below shows the jumper,
including normally open toggle switches.

5. Connect the drive to a 100/240 VAC, 50/50 Hz power source

appropriate to the drive:

• Single Phase: 1398-DDM-010, 1398-DDM-010X,

1398-DDM-020, 1398-DDM-020X, 1398-DDM-030,
1398-DDM-030X, 1398-DDM-075 or 1398-DDM-075X

• Three Phase: 1398-DDM-075, 1398-DDM-075X,

1398-DDM-150 or 1398-DDM-150X