Publication 1398-5.0 – October 1998

11-8

Maintenance and Troubleshooting

Channel BM line

07

Bad connections

Verify continuity of the
encoder cable and connec-
tors.

Verify continuity of the BM+
and BM- wiring signals.

Bad Encoder

Replace the motor or the
encoder.

Channel AM line

08

Bad connections

Verify continuity of the
encoder cable.

Verify continuity of the AM+
and AM- wiring signals.

Bad Encoder

Replace the motor or the
encoder.

Bus Undervoltage

09

Low AC line/AC power input
(100 V AC minimum for safe
drive operation)

Verify voltage level of the
incoming VAC power.

Check main VAC power
source for glitches or line
drop (below 90 VAC).

Install an uninterruptible
power supply (UPS) on your
VAC input.

Bus Overvoltage

10

Excessive regeneration of
power
When the drive is driven by
an external mechanical
power source, it may regen-
erate too much peak energy
through the drive’s power
supply. The system faults to
save itself from an overload.

Change the deceleration or
motion profile and/or reduce
the reflected inertia of your
mechanical system.

Use a larger system (motor
and drive).

Excessive AC input voltage

Verify input is below 264
VAC.

Output short circuit

Check for shorts.

Motor cabling wires shorted
together

Check for shorts.

Internal motor winding short
circuit

Check for shorts.

Illegal Hall State

11

Incorrect phasing

Bad connections

Check the Hall phasing.

Verify the Hall wiring.

RESERVED

12

RESERVED

13

RESERVED

14

RESERVED

15

RESERVED

16

Table 11.1:

Troubleshooting Guide

(continued)

Problem or Symptom

Error Code

Possible Cause(s)

Action/Solution