Publication 1398-5.0 – October 1998

Maintenance and Troubleshooting

11-9

Excessive Average Current

17

Excessive time at peak cur-
rent

Reduce acceleration rates
Reduce duty cycle (ON/
OFF) of commanded
motion.
Increase time permitted for
motion.

User larger drive and motor.

Software parameter set too
low

Increase Average Current
parameter to a less restric-
tive setting.

Insufficient bus voltage

Correct the under voltage
condition or intermittent AC
power or install a larger size
transformer.

Motor Overspeed

18

OVERSPEED parameter in
the drive set to low for the
application

Using ULTRA Master (refer
to Drive Parameters section)
set Overspeed parameter to
an acceptable range for the
application.

Motor commanded to run
above Overspeed setting

Reduce command from
position controller or change
velocity parameter in the
position controller.

Motor Phasing is incorrect

Check motor phasing.

Motor encoder phasing is
incorrect

Check encoder phasing.

Excess Following Error

19

Software position error limit
was exceeded

Increase the feed forward
gain to 100%.

Increase the following error
window (refer to
ULTRA Master Drive Param-
eters section).

Retune the drive to reduce
the following error.

Increase the slew limit win-
dow (refer to ULTRA Master
Drive Parameters).

Motor Encoder State Error

20

Motor encoder encountered
an illegal transition

Replace the motor/encoder

Use shielded cables with
twisted pair wires.

Route the feedback away
from potential noise
sources.

Check the system grounds.

Bad encoder

Replace motor/encoder.

Table 11.1:

Troubleshooting Guide

(continued)

Problem or Symptom

Error Code

Possible Cause(s)

Action/Solution