Important points, Program example – Yaskawa MotionSuite Series Machine Controller Programming Manual User Manual

Page 71

Advertising
background image

MotionSuite™ Series Machine Controller Programming Manual

Chapter 2: Motion Commands

2-30

Important Points

• T0: Positioning time=0.
• If there is 0 axis, an alarm occurs to indicate the moving amount.

Supplement

After executing the time designation positioning (MVT), the value of parameter 30 “Fast

feed speed (OLxx22)” of each axis used by the MVT command, is rewritten. Therefore,
the speed set up by the VEL command “Feed speed change” is also rewritten. The feed
speed must be set up again by the VEL command after executing the MVT command.

!

!

!

! Program Example

The program example of the time designation positioning (MVT) in the ABS mode is
shown as follows:

ABS;
MVT [axis1]100 [axis2]200 T1000;

Filter time constant

Figure 2.21: Positioning Time Delay When Using Filter

axis2

axis1

Current position

Target position

Taking 1 sec to move

200

0

100

Figure 2.22: Program Example of the Time Designation Positioning (MVT)

Advertising