Step

Display/Result

5.

Press

to select LOCAL. The LO/RE light will turn on.

STOP

6.

Press

to run the motor at 5 Hz. The RUN light will turn on.

STOP

Off

On

7.

With SW1 closed, the drive runs the motor at Multi-Step Speed 2

(20 Hz).

8.

With SW1 open and SW2 closed, the drive runs the motor at

Multi-Step 3 (50 Hz).

9.

With both SW1 and SW2 closed, the drive runs the motor at

Multi-Step 4 (60 Hz).

10. Press

STOP

to stop the drive. The RUN light will flash until the

motor comes to a complete stop.

STOP

Flashing

Off

<1>

When the frequency reference is assigned to the LED operator (b1-01=0), the first step in a multi-step speed
sequence comes from d1-01.

Note:

When a run command is input from the control circuit terminal, the frequency reference value is selected

as follows:

When b1-01 = 0 and the run command is given, the drive uses the frequency set to d1-01.

When b1-01 = 1 and the run command is given, the drive uses the frequency reference value input to

analog control terminal A1.

4.5 Basic Operation

100

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide