Close-up of V/T2-phase wiring

1st pass

4th pass

3rd pass

2nd pass

D

E

F

C

B

A

Pass each wire (U/T1, V/T2, W/T3)
through the core 4 times.

R/L1

S/L2

T/L3

U/T1

V/T2

W/T3

A – Power supply
B – MCCB
C – Zero-phase reactor on

input side

D – Drive
E – Zero-phase reactor on

output side

F – Motor

Figure 7.10 Zero-Phase Reactor

u

Installing Fuses on the Input Side

Always install input fuses to the input side of the as a protective measure against damage

caused by a short circuit.

Refer to Factory Recommended Drive Branch Circuit Protection on page 258

for details

on input fuse selection.

u

Attachment for External Heatsink

An external attachment can be used to project the heatsink outside of an enclosure to ensure

that there is sufficient air circulation around the heatsink. This installation method still requires

a certain amount of airflow over the drive case.

Refer to Output Current Derating Due to

Ambient Temperature on page 211

if derating is required. Contact a Yaskawa sales

representative for more information.

u

Noise Filter Installation

This drive has undergone testing in conformance with IEC/EN 61800-5-1 and is in compliance

with low voltage directives.

Refer to EMC Guidelines Compliance on page 248

for

information on selecting a noise filter.

u

Installing a Motor Thermal Overload (oL) Relay on the Drive
Output

Motor thermal overload relays protect the motor by disconnecting power lines to the motor

due to a motor overload condition.
Install a motor thermal overload relay between the drive and motor: