• Disable motor protection (L1-01 = 1) when running multiple motors from the same drive.

Attach a thermal relay for each motor to provide overload protection.

• Use L1-13 (Continuous Electrothermal Operation Selection) to select whether the

electrothermal value is “held” or “not held” when power supply is turned off. Default setting

is 1 (Enabled).

• In the case of a general purpose (standard) motor, the cooling capability is reduced at a low

speed. Motor overload protection (oL1) may occur in frequencies lower than motor rated

current. Use an exclusive-use or inverter-duty motor to operate the drive at rated current at

low frequency.

u

Drive Status Monitors: U1-01 to U4-13

Parameter group U displays various data regarding the operating status of the drive.
The following example demonstrates viewing output voltage reference (U1-06).

Step

Display/Result

1.

Turn on the power to the drive. The initial display appears.

2.

Press

until “Monitor Display” appears.

3.

Press

to enter the Parameter Setting Screen.

4.

Press

until U1-06 appears.

5.

Press

to display the voltage reference. The Output Voltage

Reference appears.

Refer to Parameter List on page 213

for more details about Drive Status Monitors.

Table 4.13 Drive Status Monitors

No.

Parameter Name

Page

U1-01 Frequency Reference

235

U1-02 Output Frequency

235

U1-03 Output Current

235

U1-06 Output Voltage Reference

235

U1-07 DC Bus Voltage

235

U1-10 Input Terminal Status

236

U1-11 Output Terminal Status

236

U1-13 Terminal A1 Input Voltage

236

No.

Parameter Name

Page

U1-19 MEMOBUS/Modbus Error Code

236

U1-25 Software Number (ROM)

236

U1-26 Software Number (Flash)

236

U2-01 Current Fault

236

U2-02 Previous Fault

236

U4-01 Accumulated Operation Time

237

U4-04 Cooling Fan Maintenance

237

U4-05 Capacitor Maintenance

237

4.5 Basic Operation

110

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

Advertising