5 alarm detection – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 143

Advertising
background image

Digital Operator Display

Minor Fault Name

Sequence error

Check the forward and reverse command sequence and correct the

problem.

Note: Motor ramps to stop when minor fault EF is detected.

YES

Digital Operator Display

Minor Fault Name

EF1

External fault (input terminal S1)
External fault at multi-function input terminal S1.

EF2

External fault (input terminal S2)
External fault at multi-function input terminal S2.

EF3

External fault (input terminal S3)
External fault at multi-function input terminal S3.

EF4

External fault (input terminal S4)
External fault at multi-function input terminal S4.

EF5

External fault (input terminal S5)
External fault at multi-function input terminal S5.

Cause

Possible Solution

Minor

Fault

(H2- =

10)

An external device has tripped an

alarm function.

Remove the cause of the external fault and reset the multi-function

input value.

YES

Wiring is incorrect.

• Ensure the signal lines have been connected properly to the

terminals assigned for external fault detection (H1- = 20 to 2F).

• Reconnect the signal line.

Multi-function contact inputs are

set incorrectly.

• Check if the unused terminals have been set for H1- = 20 to 2F

(External Fault).

• Change the terminal settings.

Digital Operator Display

Minor Fault Name

oH

Heatsink Overheat
The temperature exceeded the value set to L8-02.

Cause

Possible Solution

Minor

Fault

(H2- =

10)

5.5 Alarm Detection