B.2 parameter table – Yaskawa J1000 Compact V/f Control Drive User Manual

Page 230

Advertising
background image

No.

Name

Description

Range Def. Mode Addr.

Hex

Pg.

L3-01

Stall

Prevention

Selection

during

Acceleration

Selects the Stall Prevention method used to prevent

excessive current during acceleration.

0: Disabled - Motor accelerates at active acceleration

rate. The motor may stall if load is too heavy or accel

time is too short.

1: General Purpose - When output current exceeds

L3-02 level, acceleration stops. Acceleration will

continue when the output current level falls below the

L3-02 level.

0, 1

<1>

1

O

48F

L3-02

Stall

Prevention

Level during

Acceleration

Used when L3-01 = 1.

100% is equal to the drive rated current.

Decrease the set value if stalling or excessive current

occurs with default setting.

0 to 150

<4>

<2>

<4>

O

490

L3-04

Stall

Prevention

Selection

during

Deceleration

When using a braking resistor, use setting "0".

0: Disabled - The drive decelerates at the active

deceleration rate. If the load is too large or the

deceleration time is too short, an ov fault may occur.

1: General Purpose - The drive decelerates at the

active deceleration rate, but if the main circuit DC bus

voltage reaches the Stall Prevention level,

deceleration will stop. Deceleration will continue

once the DC bus level drops below the Stall

Prevention level.

4: Overexcitation Deceleration - Decelerates with the

flux level determined by n3-13 (Overexcitation

Gain).

0, 1, 4

1

S

492

L3-05

Stall

Prevention

Selection

during Run

Selects the Stall Prevention method to use to prevent

drive faults during run.

0: Disabled - Drive runs a set frequency. A heavy load

may cause the drive to trip on an oC or oL fault.

1: Decel Time 1 - The drive will decelerate at Decel

Time 1 (C1-02) if the output current exceeds the level

set by L3-06. Once the current level drops below the

L3-06 level, the drive will accelerate back to its

frequency reference at the active acceleration rate.

2: Decel Time 2 - Same as setting 1 except the drive

decelerates at Decel Time 2 (C1-04).

When output frequency is 6 Hz or less, Stall

Prevention during run is disabled regardless of the

setting in L3-05.

0 to 2

1

O

493

L3-06

Stall

Prevention

Level during

Run

Enabled when L3-05 is set to "1" or "2". 100% is

equal to the drive rated current.

Decrease the set value if stalling or excessive current

occurs with the default settings.

Upper level is determined by C6-01 and L8-38.

30 to

150

<4>

<2>

<4>

O

494

L4: Frequency Detection

Use L4 parameters to configure frequency detection operation.

L4-01

Speed

Agreement

Detection

Level

These parameters configure the multi-function output

(H2- 01 = 2, 4, 5) settings "Speed Agree 1",

"Frequency Detection 1," and "Frequency detection

2".

0.0 to

400.0

0.0

Hz

O

499

B.2 Parameter Table