Table 4.12 Motor Type and Overload Tolerances

L1-01

Setting

Motor Type

Overload Tolerance

Cooling Ability

Overload

Characteristics

1

General-

Purpose

Motor

(Standard

Self-Cooled)

Motor designed to operate

from line power.

Motor cooling is most

effective when running at

rated nameplate base

frequency (check the motor

specifications).

Operating continuously

at less than line power

frequency can trigger

motor overload

protection (oL1). A fault

is then output and the

motor will coast to stop.

2

Drive

Dedicated

Motor

(Constant

Torque, 1:10)

100

150

110

100120 167 200

55

50

0

Rated Speed=100% Speed

60 sec.

Continuous

A

D

B

(60 Hz)

Speed (%)

Torque (%)

Motor is designed to

effectively cool itself at

speeds as low as 6 Hz.

Continuous operation

with 100% load from 6

Hz to 50/60 Hz.

Notes on Motor Protection

• Motor protection meeting UL and cUL standards is achieved with the motor overload

protection time (L1-02) set to factory default setting. Normally, L1-02 (Motor Overload

Protection Time) does not require setting. If the motor overload tolerance is clear, set the

overload protection time at hot start according to the motor. To detect overload earlier,

decrease the setting.

Figure 4.19

illustrates motor protection operation time characteristics.

10

7

3

1

0.4

0.1

0

100

200

150

Cold Start

Hot Start

Motor Current (%)
E2-01 = 100%

Operation Time (minutes)

Figure 4.19 Motor Protection Operation

4.5 Basic Operation

YASKAWA ELECTRIC TOEP C710606 26D YASKAWA AC Drive – J1000 Quick Start Guide

109

4

Start-Up Programming & Operation